If after the time set for Tmax prod (in minutes, default 30), the low water level has not been reached, atomised water production is stopped and the wait procedure starts (see the description in Tmax fill), after which the control attempts to resume production. If the condition remains, alarm EP will be activated, shutting down the unit. If after a percentage of Tmax prod, set on screen Gea03 (default 70%) the water level is above the high level for a time equal to “Max Hlev time”, atomised water production stopsand warning EL is generated. The wait procedure then starts, after whichthe controller will attempt to restart production. Warning EL is reset at theend of a production cycle that ends correctly. Alarm EL is also generatedduring standby if an abnormal water level is measured (the water leveldiff ers from the level measured when switching to standby, for a timeequal to Max Hlev time).