3.5 FIELD QUALITY CONTROL
A. Inspection and Testing: Comply with NFPA 13 and Local Fire Department requirements.
B. Testing: Perform test to determine compliance with specified requirements in presence of
Contracting Officer.
1. Test, inspect, and approve piping before covering or concealing.
2. Hydrostatically test each system at 1 380 kPa (200 PSI) for 2 hour period with no leakage or
reduction in pressure.
3. Flush piping with potable water in accordance with NFPA 13.
4. Test alarms and other devices. Test water flow alarms by flowing water through inspector's
test connection.
5. Correct defects and make additional tests until systems comply with contract requirements.
6. When tests have been completed and corrections made, submit signed and dated certificate
as specified in NFPA 13.
3.6 DEMONSTRATION
A. Demonstration: Demonstrate equipment and systems.
3.7 SCHEDULES
A. Provide wet pipe fire sprinkler system as selected in following schedule:
______ Fire Protection Water Supply: Provide fire protection water supply from ____________
_________________ to _____________________________________________.
______ Locations: Provide wet pipe fire sprinkler system at following areas:
______ Provide wet pipe fire sprinkler system at following areas:
______ ________________________________________________.
______ ________________________________________________.
______ ________________________________________________.
______ ________________________________________________.
______ As indicated on Drawings.