6.3 Design, Construction, and Capacity of Storage Cabinets.<br>6.3.1 The volume of Class I, Class II, and Class IlIA liquids stored in a storage cabinet shall not exceed 454 L (120 gal).<br>6.3.2 The number of storage cabinets located in anyone fire area shall not exceed three.<br>Exception No.1: In an industrial occupancy, additional storage cabinets, in groups of not more than three cabinets, shall be permitted to be located in the same fire area, if a minimum separation of 30 m ( 100 ft) is maintained between each group.<br>Exception No.2: In an industrial occupancy that is protected by an automatic sprinkler system that is designed and installed in accordance with NFPA 13, Standard for the Installation of sprinkler Systems, the number of cabinets in anyone group shall be permitted to be increased to six.