GE didn’t reply SBR’s question directly. GE shall provide the calculation to verify whether the capacity of exhausting fan to meet the design or not.Please explain how the Argon gas at basement will be exhaust together with 1st floor. Although GE claimed the 1st floor P.TR room and B1 floor cable room belong to one fire-proof area, but these two rooms are different space respectively.