D. Reports shall all have the time and date at which they were output recorded on them.
Reports shall be formatted in such a manner as to make them easily understandable to the
operator.
E. A menu of reports shall enable the operator to access any report on the BMS. Each report
shall contain the date and time.
F. The operator shall be able to configure customized reports. Standard and customized
reports shall be configured through the BMS. Use of third party reporting packages is not
allowed.
G. The BMS Specialist shall configure the reports in accordance with the requirements of the
Employer.
3.9 SOFTWARE OPERATING SYSTEM: EVENT MESSAGES
A. The operator shall create messages up to 64 characters in length, at minimum, which shall
be displayed upon the occurrence of a particular event. There shall be capacity for 1000
event messages at any one time and the operator shall be able to associate a single message
with more than one occurrence and shall be able to associate more than one event message
with a particular event.
B. The event message shall be output at all devices selected on-line by the operator using an
interactive procedure.
C. The operator shall be able to associate one or more event messages with the following
events:
1. An alarm
2. A change of status.
3. The return to normal of an alarm condition.
4. An operator entered schedule.
5. Any other event initiated by the BMS or monitored by the BMS.