EMC Conformity Standards “◊”: C€ 5 〇N200
EN61326-1 Class A, Table 2 (For use in industrial lications)
EN61326-2-3
Communication Requirements BRAIN
Communication Distance;
Up to 2 km (1.25 miles) when using CEV polyethyl-ene-insulated PVC-sheathed cables. Communication distance varies depending on type of cable used.
Load Capacitance;
0.22 or less (see note)
Load Inductance;
3.3 mH or less (see note)
Input Impedance of communicating device;
10 kQ or more at 2.4 kHz.
Note: For general-use and Flameproof type.